TORKEL 860 Battery Load Unit
TORKEL 860 MULTI Battery Load Unit is designed primarily for people who travel from place to place to maintain battery systems having different voltages. It features excellent discharging capacity plus a broad voltage range and outstanding portability – a unique combination.
TORKEL 860 is used for systems ranging from 12 to 480 V, and discharging can proceed at up to 110 A. If higher current is desired, two or more TORKEL 860 units or extra load units, TXL, can be linked together. Discharging can take place at constant current, constant power, constant resistance or in accordance with a preselected load profile.
Testing can be carried out without disconnecting the battery from the equipment it serves. Via a DC clamp-on ammeter, TORKEL measures total battery current while regulating it at a constant level.
The TORKEL is connected to battery, the current and the voltage alarm level are set. After starting the discharge TORKEL keeps the current constant at the preset level. When the voltage drops to a level slightly above the final voltage, TORKEL issues an alarm. If the voltage drops so low that there is a risk for deep discharging the battery, TORKEL shuts down the test. The total voltage curve and the readings taken at the end of the test are stored in TORKEL Later, using the TORKEL Win program (optional), you can transfer these readings to your computer for storage, printout or export. If your PC is connected to TORKEL during the test, TORKEL Win builds up a voltage curve on the screen in real time and displays the current, voltage and capacity readings.
ESS Code: HBTE.3
- Batteries can be tested “in service”
- Unit adjusts to include load currents in the test parameters
- User adjustable alarm and shutdown points to avoid excessive discharge
- Easily expandable for larger battery banks using TXL extra load units
- View test parameters/results “real time” as testing progresses using TORKEL WIN software (optional)
- Easily save results to a PC for analysis, report generation and storage
- External measurement input used to measure current in an external path by means of a clamp-on ammeter or a current shunt.
- Keys for operation and settings.
- Alarm output equipped with a relay contact for triggering an external alarm device.
- Start/Stop input used for starting and stopping discharging from an external device. Galvanically isolated.
- Indicating lamps. Operating, Stop/Limit
Set up an Account
Login or create an account to gain access to your account history and document library. Link your Web Account to your ESS Credit account to hire online, contact us for details.
TORKEL 860 Battery Load Unit
hire Price
ESS Code: HBTE.3Rates exclude VAT and Damage Waiver
£594.00 Ex. VAT
Minimum hire period: 5 days
Lead time: 1 day
Please note you will be charged for the minimum hire period if your order is for a period less than this. A web account linked to your ESS Credit account is required to hire online.
Key Product Features
Unit adjusts to include load currents in the test parameters
User adjustable alarm and shutdown points to avoid excessive discharge
Easily expandable for larger battery banks using TXL extra load units
External measurement input used to measure current in an external path by means of a clamp-on ammeter or a current shunt.
Open your ESS Account Today
An ESS Credit Account linked to your Web Account is required to hire products online.
Trading with ESS is quick and simple with an ESS account. An ESS Web Account allows you to hire online, access to the MyAccount area and our Technical Document library. Link this to an ESS Credit Account to Hire online and get reporting on your hires in the MyAccount area too.
Already have an ESS Credit Account? You can request we link your web and credit accounts here.
Contact us for further details.