B2 HVA120 120 kV VLF Tester
The compact B2 HVA120 delivers sinusoidal VLF and DC testing up to 120 kV peak, offering continuous, maintenance-free performance with reporting and sheath fault diagnostics—ideal for UK cable diagnostics and high‑voltage commissioning.
Built by b2 electronics, the HVA120 combines portability with industry-leading test power––ideal for medium-voltage cable networks up to 69 kV per IEEE 400.2‑2013 and CENELEC standards. Its dry transformer design avoids oil and eliminates routine servicing, while the dual discharge system ensures operator safety with integrated 12 kV feedback protection
Test capabilities include VLF withstand, DC hipot, sheath and jacket testing, sheath fault location, vacuum bottle testing, cable fault conditioning (“burning”) and advanced diagnostics. The integrated real-time oscilloscope displays load capacitance and charging current, while RMS metering of voltage, current, capacitance and resistance is built-in
Scope for industries: utilities, renewable energy, rail, infrastructure, industrial plants and UK grid maintenance teams. Typical uses: commissioning new XLPE or EPR cables, fault finding, sheath integrity verification on pipelines or power cables, transformer and switchgear insulation checks. Every hire includes the b2 ControlCenter software for test sequence programming and USB or RS‑232 reporting
Hiring in the UK means next‑day delivery with full calibration traceability. Contact us today to arrange your HVA120 hire.
ESS Code: HVLF.8
- VLF sinewave up to 120 kV peak / 85 kV RMS
- DC ±100 kV and square wave up to 100 kV
- Continuous operation, no thermal limit
- Dry, maintenance free high voltage system
- Dual Discharge Device + 12 kV feedback protection
- Real-time on unit oscilloscope and RMS metering
- Programmable test sequences and USB/RS 232 export
- Sheath fault location, conditioning, vacuum bottle test
- Expandable to Tan Delta or Partial Discharge diagnosis
Set up an Account
Login or create an account to gain access to your account history and document library. Link your Web Account to your ESS Credit account to hire online, contact us for details.
B2 HVA120 120 kV VLF Tester
hire Price
ESS Code: HVLF.8Rates exclude VAT and Damage Waiver
£1,990.00 Ex. VAT
Minimum hire period: 5 days
Lead time: 3 days
Please note you will be charged for the minimum hire period if your order is for a period less than this. A web account linked to your ESS Credit account is required to hire online.
Key Product Features
Up to 120 kV peak / 85 kV RMS VLF sinusoidal output
Operates continuously with no thermal limitation
Dry‑type design (oil‑free) requiring minimal maintenance
Dual Discharge Device and 12 kV feedback protection for safety